PSEMIC ENGINEERING RESOURCE CENTRE

Water Treatment, Flushing & Chemical Dosing Calculators for HVAC & Chilled Water Systems

Practical engineering tools for chilled-water flushing, system water volume, circulation, inhibitors, chemical cleaning, glycol mixing, dilution, dosing pumps, conductivity/TDS and water-treatment planning.

Engineering & safety note: Final chemical selection, dosage, compatibility, exposure time, discharge, handling and PPE must follow the chemical manufacturer's current TDS/SDS, approved method statement and project specification. Never mix chemicals unless compatibility has been explicitly confirmed.
01 · SYSTEM CAPACITY

Chilled Water System Volume Calculator

Estimate water volume contained in pipework and add known equipment or tank volumes.

Pipe Volume—
Total System Volume—
Total Litres—
US Gallons—
Pipe volume = π × ID² ÷ 4 × length.
02 · FLUSHING

Flushing Flow Rate & Velocity Calculator

Calculate required water flow for a target flushing velocity or check achieved velocity from available flow.

Required flow from target velocity

Required Flow—
Litres / Second—
USGPM—

Achieved velocity from available flow

Achieved Velocity—
Use the flushing velocity required by the approved commissioning procedure or project specification.
03 · CIRCULATION

System Turnover & Flushing Water Calculator

Estimate time per turnover and total circulation time.

Time / Turnover—
Total Circulation Time—
Water Equivalent—
04 · CHEMICAL DOSING

Chemical Dose by ppm Calculator

Calculate indicative commercial product quantity from system volume, target active concentration and product strength.

Active Chemical Required—
Commercial Product Mass—
Commercial Product Volume—
This calculator does not determine the correct treatment concentration. Use only supplier/project-approved dosage.
05 · SUPPLIER DOSING

Manufacturer Recommended Dose Calculator

Scale an approved dosage such as 2 L per 1,000 L to the actual system capacity.

Required Product—
06 · INHIBITOR MANAGEMENT

Corrosion Inhibitor Top-Up Calculator

Estimate additional active inhibitor required to move from a measured level to an approved target.

Concentration Increase—
Active Chemical—
Commercial Product—
07 · SOLUTION PREPARATION

Chemical Dilution Calculator — C₁V₁ = C₂V₂

Calculate stock solution and dilution water needed for a lower-concentration solution.

Stock Solution Required—
Dilution Water—
Do not use this tool to determine mixing sequence. Follow SDS/TDS instructions exactly.
08 · HVAC GLYCOL

Glycol Concentration & Top-Up Calculator

Estimate glycol and water quantities for a new mix or concentration increase.

Glycol Volume—
Water Volume—

Increase existing concentration

Approx. Glycol to Add—
Verify freeze protection and maximum concentration using the approved glycol manufacturer's data.
09 · DOSING EQUIPMENT

Chemical Dosing Pump Rate Calculator

Estimate product feed rate from water flow and an approved active dosage.

Product Feed Rate—
Daily Product Use—
Approx. Pump Setting—
10 · GENERAL WATER CHEMISTRY

General Water Treatment Calculators

Supporting calculations for conductivity/TDS, ppm, storage, treatment cost, batch concentration and project limit checks.

Conductivity → Approx. TDS

Approx. TDS—

ppm ↔ mg/L

Dilute Water Approximation—

Chemical Storage Days

Stock Autonomy—

Treatment Cost per m³

Chemical Cost / m³—

Batch Tank Chemical Quantity

Indicative Product Volume—

Water Quality Limit Check

Status—

Need a CHW Flushing, Cleaning or Water-Treatment Plan?

For chilled-water flushing, pressure testing, chemical cleaning, system circulation and commissioning, contact the PSEMIC engineering team for project-specific support.

Get Expert Advice from PSEMIC